Size starter-to-house alternator charger wiring for zero voltage-sense dropouts
Popular 50 A dual solar + alternator DC-DC chargers run continuously at rated amps whenever driving, and a 16 ft path from starter post to rear electrical cabinet equals 32 ft of round-trip copper.
Holding a 3% loop budget at 12.8 V (0.384 V max) over 16 ft takes 3 AWG marine copper (or accessible 2 AWG cable) with a 75 A MRBF or 80 A ANL fuse—while short 8 ft runs fit comfortably on 6 AWG (2.86% drop).
Formulas
3% round-trip ceiling at 12.8 V = 0.384 V max loss16 ft one-way (32 ft loop) on 3 AWG @ 50 A = 0.365 V (2.85% drop)8 ft run @ 50 A = 6 AWG (0.366 V, 2.86% drop, 67 A limit)
Worked example
At 50 A across a 16 ft one-way van run (12.8 V, 75 °C terminals), 3 AWG clears the 3% threshold at 2.85% drop (0.365 V) with a 75 A MRBF / 80 A ANL fuse; shortening to 8 ft lets 6 AWG pass at 2.86%.