Size 48 V Victron Lynx Distributor feeders and high-AIC Class T protection
The Victron Lynx Distributor uses a 1,000 A internal copper busbar with M8/M10 studs and four MEGA fuse positions, making it a popular hub for 48 V LiFePO4 banks, SmartSolar MPPTs and MultiPlus-II inverters.
At 58.4 V peak LiFePO4 absorption, standard 32 V automotive MEGA fuses are unsafe and even 58 V / 70 V MEGA fuses carry lower AIC than Class T. Install a 125 V Class T fuse (via Lynx Class-T Power In or external holder) directly off the battery bank and size the trunk for 125% continuous current.
Formulas
125% trunk fuse target @ 180 A = 225 A (Class T 125 V DC)5 ft one-way loop = 3.048 m · 3/0 AWG copper drop ≈ 0.13 V (0.25%)Dual-inverter 250 A trunk → 125% = 312.5 A (exceeds single 4/0 90 °C leg)
Worked example
A 180 A 51.2 V Lynx trunk over 5 ft one-way selects 3/0 AWG copper (231 A marine 90 °C ampacity, 0.25% drop) with a 225 A Class T fuse; a 250 A dual-inverter bank pushes past single 4/0 limits at 90 °C terminals and calls for parallel 2/0 legs or 105 °C lugs.