Convert Victron MultiPlus-II 48/5000 metric specs cleanly between AWG and mm²
At 4,000 W continuous inverter output (~90% efficiency) or full 70 A charging plus transient surge, a 48 V 5000 VA inverter-charger typically operates around 90–100 A continuous DC near low-battery cutoff.
At 2 m one-way, 3 AWG (~26.7 mm²) holds loop drop at 0.61% (0.31 V) and matches a 125 A Class T fuse; installers using metric European cables step cleanly up to 35 mm² (~2 AWG) or 50 mm² for multi-unit parallel banks or 5 m runs.
Formulas
125% fuse screen at 100 A = 125 A Class T2 m one-way loop (4 m total) on 3 AWG = 0.31 V (0.61% drop)5 m one-way loop (10 m total) on 3 AWG = 0.79 V (1.54% drop)
Worked example
At 100 A over 2 m one-way using 105 °C marine copper, 3 AWG (26.7 mm²) yields 0.31 V (0.61%) drop with a 125 A Class T fuse; extending to 5 m keeps the same 3 AWG run at 1.54% drop (0.79 V).