Victron MultiPlus-II 48/5000 Cable Gauge & DC Fuse Size

Check metric mm² and AWG DC battery cable sizing, 2% round-trip voltage drop and 125 A Class T protection for a 48 V 5000 VA inverter-charger.

Jump to results

Inputs

Circuit and voltage drop
Use full charge voltage when screening DC fuses.
Cable and installation
Enter the combined ambient and bundling adjustment.

Results

Estimates
Minimum reference gauge3 AWG
Round-trip length
4 m
Fuse target at 125% load
125 A
Copper or aluminum area
26.67 mm²
Calculated drop
0.31 V · 0.61%
Cable loss
31.45 W
Adjusted ampacity
126 A
DC circuit loop schematic · Copper · Marine bundle3 AWG · 0.61% drop
DC POWER LOOP · COPPER · MARINE BUNDLE · 105 °C PASS · 3 AWG (26.7 mm²) BATTERY / SOURCE 51.2 V Max 58.4 V DC Draw 100 A MAIN FUSE Class T 125 A Ceiling 125 V DC 3 AWG · 26.7 mm² Cu 2 m 1-way · 0.79 Ω/km @ 75 °C LOAD / INVERTER 50.89 V At load terminals 5,120 W · 100 A Return conductor (3 AWG · 4 m round-trip) · Drop −0.31 V VOLTAGE DROP VS. 2% 0.61% Drop 0.31 V / 1.02 V max Loss 31.4 W AMPACITY (100% DERATE) 100 / 126 A 125% fuse target 125 A Fuse cap 126 A
Neighboring gauges
AWGmm²Ω/kmAmpacityDropScreen
613.31.57684 A1.23%Outside limits
421.150.991112 A0.77%Outside limits
326.670.786126 A0.61%Pass
233.630.623147 A0.49%Pass
142.410.494172 A0.39%Pass
Main fuse candidates
TypeCurrent candidateExample DC ceiling
Class T125 A125 V
ANLNo fit in reference range32 V
MRBFNo fit in reference range58 V

Fuse candidates account for the entered 58.4 V circuit maximum. Check available fault current, interrupt rating, terminals and applicable installation rules.

Engineering Bill of Materials (BOM)
CategorySpecificationQtySizing basis
DC Cable Run3 AWG (26.67 mm²) copper cable, 105 °C (marine)4 m loop (2 m × 2)0.61% drop (0.31 V) · 126 A ampacity
Main DC Fuse & HolderClass T 125 A fuse (125 V DC) + compatible holder1 set125% load (125 A) screened @ 58.4 V max
Lugs & Terminations3 AWG tinned copper compression lugs + heat shrink4 lugsRated ≥105 °C terminal limit for copper
DC Busbar150 A DC distribution busbar pair with insulated cover1 pair (+ / −)Covers ≥125 A continuous feeder rating
DC Isolator Switch150 A DC load-break isolator (≥59 V DC)1 unitManual disconnect for 100 A 51.2 V circuit

Convert Victron MultiPlus-II 48/5000 metric specs cleanly between AWG and mm²

At 4,000 W continuous inverter output (~90% efficiency) or full 70 A charging plus transient surge, a 48 V 5000 VA inverter-charger typically operates around 90–100 A continuous DC near low-battery cutoff.

At 2 m one-way, 3 AWG (~26.7 mm²) holds loop drop at 0.61% (0.31 V) and matches a 125 A Class T fuse; installers using metric European cables step cleanly up to 35 mm² (~2 AWG) or 50 mm² for multi-unit parallel banks or 5 m runs.

Formulas

  • 125% fuse screen at 100 A = 125 A Class T
  • 2 m one-way loop (4 m total) on 3 AWG = 0.31 V (0.61% drop)
  • 5 m one-way loop (10 m total) on 3 AWG = 0.79 V (1.54% drop)

Worked example

At 100 A over 2 m one-way using 105 °C marine copper, 3 AWG (26.7 mm²) yields 0.31 V (0.61%) drop with a 125 A Class T fuse; extending to 5 m keeps the same 3 AWG run at 1.54% drop (0.79 V).

Engineering references

Frequently asked questions

Which metric cable cross-section corresponds nearest to 3 AWG or 2 AWG copper?

2 AWG equals 33.6 mm² (35 mm² European standard H07V-K / marine flex), while 1/0 AWG sits cleanly alongside 50 mm² battery cable.

Do I need pre-charge protection on a MultiPlus-II 48/5000 DC bank?

Large inverter input capacitors draw brief inrush sparks on initial connection, so switching the BMS safely or pre-charging through a power resistor protects contactor tips and fuses.

Why does Lynx Distributor Mega 58 V rating clash with 58.4 V absorption?

Always verify fuse DC voltage ratings at maximum pack charge voltage—16S LFP at 58.4 V calls for 70 V–125 V Class T or high-voltage MIDI/MEGA variants rather than 58 V parts.