DC Contactor Breaking Current vs. Fuse Clearing

Check the fault-current gap between the maximum contactor breaking current and the minimum assured fuse breaking current.

Jump to results

Inputs

Pack and load
Include both conductors and the rest of the fault loop.
Fuse and contactor data
Use the datasheet factor for temperature, mounting and duty.
Use applicable DC test data at the stated fault conditions.
Use the voltage at which the entered breaking limit applies.
Include detection, command and mechanical delays.
Enter the applicable closed-contact withstand from the damage curve.

Results

Estimates
Maximum prospective bolted fault2.668 kA
Nominal prospective fault
2.353 kA
Fault loop resistance
170 mΩ
Pre-arcing time proxy at max voltage
2.528 ms
Clearing time proxy at max voltage
5.618 ms
Clearing proxy at nominal voltage / withstand limit
7.225 ms / 10 ms
Fuse-first proxy / earliest contact parting
6.4 ms / 8 ms
Surge I²t / pre-arcing margin
6,760 A²s / 2.66 ×
Total clearing I²t / withstand margin
40,000 A²s / 1.5 ×
Derated continuous fuse limit
160 A
DC voltage headroom
46.4 V
Coordination screen
Review failed checks
Bolted fault and DC breaking limits
Maximum prospective fault 2.668 kA Contactor breaking limit 2.5 kA Fuse interrupt rating 20 kA
Coordination checks
CheckScreen
Continuous fuse loadWithin entered limit
Surge vs. fuse pre-arcing I²tWithin entered limit
Total clearing I²t vs. protected pathWithin entered limit
Clearing proxy vs. contactor withstand timeWithin entered limit
Prospective fault vs. fuse breaking rangeOutside entered limit
Fuse/contactor minimum break overlapOutside entered limit
DC voltage and arc rating inputsWithin entered limit
Fuse clearing proxy vs. earliest contact partingWithin entered limit

Check actual DC time-current bands and arcing data at the applicable polarity, L/R and worst-case operating conditions.

DC Contactor Breaking Current vs. Fuse Clearing method

Check the fault-current gap between the maximum contactor breaking current and the minimum assured fuse breaking current.

The prospective bolted fault uses a resistive Thévenin estimate at nominal and maximum pack voltage. Series cell groups add resistance, matched parallel branches reduce it and the entered external loop includes both conductors. Evaluate the full expected voltage, SOC, temperature, age and fault-path impedance range separately.

Melting I²t represents pre-arcing. Total clearing I²t includes arcing and is compared with the weakest path withstand. Dividing by prospective current squared gives a constant-current time proxy. Current limitation, arc voltage, DC time constant and preheating can make real clearing time differ substantially.

When prospective current exceeds the contactor breaking limit, compare estimated fuse clearing before contact parting and against the damage envelope. Check datasheet time-current bands, minimum and maximum interrupt current, DC polarity, circuit L/R, voltage transients and the tested fuse-contactor combination.

Formulas

  • Rloop = (Ns × Rcell / Np + Rexternal) / 1000 with input resistances in mΩ; Iprospective = Vpack / Rloop
  • Constant-current time proxy = I²t / Iprospective²; surge I²t = Isurge,rms² × pulse duration
  • Thermal margin = protected path withstand I²t / fuse total clearing I²t
  • DC voltage headroom = min(fuse DC rating, contactor DC rating at the entered breaking current) − maximum bus voltage

Worked example

The starting scenario gives 2.668 kA prospective current at maximum bus voltage and a 5.618 ms constant-current clearing proxy. The thermal margin ratio is 1.5.

Engineering references

Frequently asked questions

Why is minimum fuse breaking current part of coordination?

A fault above the contactor’s limit and below the fuse’s minimum breaking current can fall outside both components’ interruption capabilities.

In the DC Contactor Breaking Current vs. Fuse Clearing example, does fuse melting mean the fault has cleared?

The element can begin arcing after melting. Compare total clearing time and let-through energy with the contactor and protected path limits.

In the DC Contactor Breaking Current vs. Fuse Clearing example, which DC contactor rating belongs in this check?

Use the DC breaking current at the applicable bus voltage, polarity and circuit L/R. Continuous carry current describes a different operating condition.