Compare fuse clearing limits with the DC contactor damage envelope
The prospective bolted fault uses a resistive Thévenin estimate at nominal and maximum pack voltage. Series cell groups add resistance, matched parallel branches reduce it and the entered external loop includes both conductors. Evaluate the full expected voltage, SOC, temperature, age and fault-path impedance range separately.
Melting I²t represents pre-arcing. Total clearing I²t includes arcing and is compared with the weakest path withstand. Dividing by prospective current squared gives a constant-current time proxy. Current limitation, arc voltage, DC time constant and preheating can make real clearing time differ substantially.
When prospective current exceeds the contactor breaking limit, compare estimated fuse clearing before contact parting and against the damage envelope. Check datasheet time-current bands, minimum and maximum interrupt current, DC polarity, circuit L/R, voltage transients and the tested fuse-contactor combination.
Formulas
Rloop = (Ns × Rcell / Np + Rexternal) / 1000 with input resistances in mΩ; Iprospective = Vpack / RloopConstant-current time proxy = I²t / Iprospective²; surge I²t = Isurge,rms² × pulse durationThermal margin = protected path withstand I²t / fuse total clearing I²tDC voltage headroom = min(fuse DC rating, contactor DC rating at the entered breaking current) − maximum bus voltage
Worked example
A 108S2P, 453.6 V pack with 1.8 mΩ per cell and 8 mΩ of external loop resistance gives a 105.2 mΩ loop and about 4.31 kA of prospective current. A 40,000 A²s clearing integral gives a 2.15 ms constant-current proxy at that current.