Compare copper cost, lug sizing and I²R heat across 12 V vs. 24 V van conversions
A 5.12 kWh lithium bank (four 12 V 100 Ah or eight 200 Ah cells) stores identical watt-hours at 12.8 V or 25.6 V, yet running a 2,500 W AC inverter at 12.8 V pulls roughly 240 A DC compared to 120 A at 25.6 V.
Cutting DC current in half quarters resistive heat loss (I²R) and shrinks required battery feeders over an 8 ft van wheel-well run from stiff 4/0 AWG + 300 A fuse down to flexible 1 AWG + 150 A fuse.
Formulas
Four-times copper benefit: halving current quarters P_loss = I² × R_loop24 V @ 120 A over 8 ft = 1 AWG (0.29 V, 1.13% drop, 150 A Class T)12 V @ 240 A over 8 ft = 4/0 AWG (0.23 V, 1.79% drop, 300 A Class T)
Worked example
Over an 8 ft one-way marine run for a 2,500 W load, 24 V (120 A) needs just 1 AWG copper (1.13% drop, 150 A Class T/MRBF), whereas 12 V (240 A) requires massive 4/0 AWG copper (1.79% drop, 300 A fuse).