24V 200Ah LiFePO4 Wire Gauge & Voltage Drop Calculator

Find a reference wire gauge for a 25.6 V, 200 Ah LiFePO4 system using load current, cable run and a 3% voltage-drop target.

Jump to results

Inputs

Circuit and voltage drop
Use full charge voltage when screening DC fuses.
Cable and installation
Enter the combined ambient and bundling adjustment.

Results

Estimates
Minimum reference gauge4 AWG
Round-trip length
10 m
Fuse target at 125% load
75 A
Copper or aluminum area
21.15 mm²
Calculated drop
0.57 V · 2.21%
Cable loss
33.96 W
Adjusted ampacity
85 A
DC circuit loop schematic · Copper · Raceway4 AWG · 2.21% drop
DC POWER LOOP · COPPER · RACEWAY · 75 °C PASS · 4 AWG (21.2 mm²) BATTERY / SOURCE 25.6 V Max 29.2 V DC Draw 60 A MAIN FUSE ANL 80 A Ceiling 32 V DC 4 AWG · 21.2 mm² Cu 5 m 1-way · 0.94 Ω/km @ 60 °C LOAD / INVERTER 25.03 V At load terminals 1,536 W · 60 A Return conductor (4 AWG · 10 m round-trip) · Drop −0.57 V VOLTAGE DROP VS. 3% 2.21% Drop 0.57 V / 0.77 V max Loss 34 W AMPACITY (100% DERATE) 60 / 85 A 125% fuse target 75 A Fuse cap 85 A
Neighboring gauges
AWGmm²Ω/kmAmpacityDropScreen
88.372.38550 A5.59%Outside limits
613.31.565 A3.52%Outside limits
421.150.94385 A2.21%Pass
326.670.748100 A1.75%Pass
233.630.593115 A1.39%Pass
Main fuse candidates
TypeCurrent candidateExample DC ceiling
Class TNo fit in reference range125 V
ANL80 A32 V
MRBF75 A58 V

Fuse candidates account for the entered 29.2 V circuit maximum. Check available fault current, interrupt rating, terminals and applicable installation rules.

Engineering Bill of Materials (BOM)
CategorySpecificationQtySizing basis
DC Cable Run4 AWG (21.15 mm²) copper cable, 90 °C (raceway)10 m loop (5 m × 2)2.21% drop (0.57 V) · 85 A ampacity
Main DC Fuse & HolderANL 80 A fuse (32 V DC) + compatible holder1 set125% load (75 A) screened @ 29.2 V max
Lugs & Terminations4 AWG tinned copper compression lugs + heat shrink4 lugsRated ≥75 °C terminal limit for copper
DC Busbar100 A DC distribution busbar pair with insulated cover1 pair (+ / −)Covers ≥75 A continuous feeder rating
DC Isolator Switch100 A DC load-break isolator (≥30 V DC)1 unitManual disconnect for 60 A 25.6 V circuit

Size a 25.6 V feeder from current and cable length

A 200 Ah battery describes stored charge. The wires carry the current demanded by the downstream loads. This example uses 60 A, equivalent to about 1.54 kW DC at 25.6 V nominal, with a 5 m one-way copper run.

The reference screen uses the full current path of 10 m and starts with a 3% drop budget. An enclosed, bundled or hot route can change ampacity. Use the battery and BMS current limits when checking the actual load and fault protection.

Formulas

  • Nominal LFP bank voltage = 8 × 3.2 V
  • Drop budget in volts = nominal volts × drop fraction
  • Drop (%) = 100 × load current × loop resistance ÷ nominal volts

Worked example

At 25.6 V, a 3% drop allows 0.768 V. The preset returns 4 AWG copper with about 0.57 V drop for a 10 m loop at 60 A. The terminal limit and fuse screening current also affect this result.

Engineering references

Frequently asked questions

Does a 24 V 200 Ah LiFePO4 battery need a 200 A cable?

Use the circuit’s continuous and surge loads for wire sizing. A bank’s 200 Ah capacity and its BMS discharge rating describe different quantities.

Should I enter 24 V or 25.6 V for the drop calculation?

Use the nominal voltage you want to reference when expressing a percentage. An 8S LiFePO4 bank has a 25.6 V nominal value, and the preset uses a separate 29.2 V maximum for fuse screening.

What if the DC load has a tight undervoltage cutoff?

Check the actual load-terminal voltage under maximum current at low battery state of charge. Include voltage loss in the cables, fuse, connectors and return path.