Victron SmartSolar MPPT 150/85 Solar String & Cold Voc Calculator

Size a 48 V or 24 V solar array for a Victron SmartSolar 150/85 MPPT charge controller, screening −15 °C cold Voc ceiling and 85 A battery output.

Jump to results

Inputs

Energy and design weather
Single panel
Battery and AC loads

Results

Estimates
Recommended installed PV2,640 W
Energy-based minimum
2,361 W
Cold Voc per panel
43.9 V
Hot Vmp per panel
27.63 V
Minimum controller start voltage
63.4 V
Inverter continuous
2,750 W
Inverter peak
4,400 W
Suggested layout
3S × 2P
MPPT PV voltage / battery output
150 V / ≥52 A
Minimum PV-side Isc allowance
35.75 A
Solar array & MPPT safety schematic3S × 2P · 150 V
PV ARRAY & MPPT SAFETY WINDOW · -15 TO 70 °C PASS · 3S2P (2,640 W) PV ARRAY (440 W) 3S × 2P 2,640 W (6 panels) Cold Voc 43.9 V/ea Hot Vmp 27.6 V/ea 35.8 A MPPT CONTROLLER 150 V / 52 A Start floor 63.4 V Safe ceiling 135 V String 83–132 V 52 A BATTERY & INVERTER 51.2 V Bus Absorb 58.4 V DC Cont. inv 2,750 W Peak surge 4,400 W MPPT VOLTAGE WINDOW (0 – 150 V CEILING) Hot 82.9 V → Cold 131.7 V Start floor ≥ 63.4 V Operating: 82.9–131.7 V (3S) Safe Voc ≤ 135 V
Controller voltage comparison
PV ceilingLayoutCold VocHot VmpPV Isc × 1.25Output amps
100 VNo fit————
150 V3S × 2P131.71 V82.9 V35.75 A52 A
250 V3S × 2P131.71 V82.9 V35.75 A52 A

Verify operating MPPT range, allowed PV wattage, battery current limits, and max PV short-circuit current on the specific controller.

Engineering Bill of Materials (BOM)
CategorySpecificationQtySizing basis
Solar PV Modules440 W PV panels (39.2 V Voc / 32.8 V Vmp)6 panels (3S × 2P)2,640 W installed ≥ 2,361 W energy target
MPPT Charge Controller150 V / ≥52 A MPPT solar charge controller1 unitCold Voc 131.71 V · Hot Vmp 82.9 V · 35.75 A PV Isc
PV Array DC Isolator & FusePV DC isolator + 36 A gPV fuse/breaker (150 V DC)1 set1.25 × PV short-circuit current with cold Voc margin
MPPT Cable & Main Fuse6 AWG (13.3 mm²) copper + Class T 75 A fuse & holder1 circuit (+ / −)125% of 52 A MPPT battery charge output @ 58.4 V
Inverter & DC Isolator2,750 W cont. / 4,400 W peak 51.2 V inverter + 75 A DC isolator1 inverter + switch125% of 2,200 W running load & 4,400 W surge
DC Busbar100 A DC distribution busbar pair1 pair (+ / −)Combines MPPT charge & inverter DC legs

Keep 3S strings safely beneath the SmartSolar 150/85 150 V PV limit

Victron’s SmartSolar 150/85 handles up to 150 V open-circuit PV input, 70 A max PV short-circuit current and 85 A continuous battery charge output (~4,900 W on 48 V or ~2,450 W on 24 V).

Using 440 W 39.2 V Voc modules at −15 °C, cold Voc climbs to 43.90 V/panel. Three panels in series reach 131.71 V (safely below the 135 V 10%-margin ceiling), while 3S × 2P (2,640 W, 52 A output) leaves clean room to expand to 3S × 3P (3,960 W, 78 A output) on one 150/85.

Formulas

  • Cold Voc @ −15 °C = 39.2 × [1 + (−0.003) × (−40)] = 43.904 V/panel
  • 3S cold Voc = 3 × 43.904 = 131.71 V < 135 V (150 V with 10% margin)
  • Hot 3S Vmp @ 70 °C = 3 × 27.634 = 82.90 V > 63.4 V start floor

Worked example

For 8,500 Wh/day at 4.5 PSH and −15 °C, six 440 W panels wired 3S × 2P (2,640 W installed, 52 A battery output, 131.71 V cold Voc, 35.75 A design Isc) fit a single SmartSolar 150/85 with headroom for a third parallel string.

Frequently asked questions

How many 440 W solar panels can a Victron SmartSolar 150/85 handle on a 48 V bank?

At 58.4 V max charge, 85 A delivers ~4,964 W—typically supporting 3S × 3P (9 panels, 3,960 W) or 3S × 4P (12 panels, 5,280 W slight over-paneling) as long as parallel Isc stays under 70 A.

Will 4 panels in series damage a SmartSolar 150/85?

Yes—four 39.2 V Voc panels reach 175.6 V at −15 °C (and 156.8 V even at 25 °C), immediately exceeding the 150 V hardware limit and voiding warranty.

What cable and fuse connect a SmartSolar 150/85 to a 48 V Lynx Distributor?

85 A × 1.25 = 106.25 A, calling for 2 AWG or 1 AWG copper (or 35 mm²) with a 125 A fuse rated ≥58 V DC.