Sol-Ark 8K-2P 48V Hybrid Inverter Battery Cable & Class T Fuse Calculator

Calculate DC wire gauge, round-trip voltage drop and Class T fuse size for a Sol-Ark 8K-2P inverter on a 51.2 V LiFePO4 battery bank.

Jump to results

Inputs

Circuit and voltage drop
Use full charge voltage when screening DC fuses.
Cable and installation
Enter the combined ambient and bundling adjustment.

Results

Estimates
Minimum reference gauge3/0 AWG
Round-trip length
3.66 m
Fuse target at 125% load
212.5 A
Copper or aluminum area
85.03 mm²
Calculated drop
0.15 V · 0.28%
Cable loss
24.8 W
Adjusted ampacity
231 A
DC circuit loop schematic · Copper · Marine bundle3/0 AWG · 0.28% drop
DC POWER LOOP · COPPER · MARINE BUNDLE · 90 °C PASS · 3/0 AWG (85 mm²) BATTERY / SOURCE 51.2 V Max 58.4 V DC Draw 170 A MAIN FUSE Class T 225 A Ceiling 125 V DC 3/0 AWG · 85 mm² Cu 6 ft 1-way · 0.23 Ω/km @ 60 °C LOAD / INVERTER 51.05 V At load terminals 8,704 W · 170 A Return conductor (3/0 AWG · 3.66 m round-trip) · Drop −0.15 V VOLTAGE DROP VS. 2% 0.28% Drop 0.15 V / 1.02 V max Loss 24.8 W AMPACITY (100% DERATE) 170 / 231 A 125% fuse target 212.5 A Fuse cap 231 A
Neighboring gauges
AWGmm²Ω/kmAmpacityDropScreen
1/053.480.373172 A0.45%Outside limits
2/067.430.296200 A0.36%Outside limits
3/085.030.235231 A0.28%Pass
4/0107.220.186270 A0.23%Pass
Main fuse candidates
TypeCurrent candidateExample DC ceiling
Class T225 A125 V
ANLNo fit in reference range32 V
MRBFNo fit in reference range58 V

Fuse candidates account for the entered 58.4 V circuit maximum. Check available fault current, interrupt rating, terminals and applicable installation rules.

Engineering Bill of Materials (BOM)
CategorySpecificationQtySizing basis
DC Cable Run3/0 AWG (85.03 mm²) copper cable, 105 °C (marine)3.66 m loop (6 ft × 2)0.28% drop (0.15 V) · 231 A ampacity
Main DC Fuse & HolderClass T 225 A fuse (125 V DC) + compatible holder1 set125% load (212.5 A) screened @ 58.4 V max
Lugs & Terminations3/0 AWG tinned copper compression lugs + heat shrink4 lugsRated ≥90 °C terminal limit for copper
DC Busbar250 A DC distribution busbar pair with insulated cover1 pair (+ / −)Covers ≥213 A continuous feeder rating
DC Isolator Switch250 A DC load-break isolator (≥59 V DC)1 unitManual disconnect for 170 A 51.2 V circuit

Size Sol-Ark 8K-2P battery conductors for 170 A continuous DC draw

The Sol-Ark 8K-2P supports 8,000 W continuous inverter output (roughly 170 A DC at 48–51.2 V under load, with 185 A max charge/discharge capability), making conductor ampacity and low voltage drop essential for clean split-phase motor starts.

At 170 A over 6 ft one-way, the 125% continuous screen targets 212.5 A—selecting 3/0 AWG copper (231 A marine 90 °C rating, 0.28% drop) and a 225 A Class T fuse, or 4/0 AWG when limited to 75 °C NEC raceway terminals.

Formulas

  • DC discharge @ 8 kW / 92% eff / 51.2 V ≈ 170 A
  • 125% NEC/fuse screening current = 170 × 1.25 = 212.5 A → 225 A Class T
  • 10 ft extended loop = 6.096 m · 3/0 AWG drop ≈ 0.24 V (0.47%)

Worked example

A Sol-Ark 8K-2P drawing 170 A over 6 ft one-way screens 3/0 AWG copper (0.28% drop) and a 225 A Class T fuse; switching to 75 °C raceway rules steps up to 4/0 AWG copper.

Engineering references

Frequently asked questions

Does the Sol-Ark 8K use one or two pairs of battery lugs?

Unlike the Sol-Ark 15K (which uses twin parallel 2/0–4/0 pairs), the 8K-2P typically connects via a single heavy copper pair (3/0 or 4/0 AWG) from a fused battery busbar.

Why should I keep battery cables under 10 ft on a Sol-Ark 8K?

Shorter, tightly twisted positive/negative pairs minimize loop inductance and voltage sag during well-pump or HVAC compressor starts.

Is a 200 A or 225 A Class T fuse better for a Sol-Ark 8K bank?

A 225 A Class T fuse clears the 125% continuous factor (212.5 A) without nuisance trips while still protecting 3/0 AWG (90 °C) or 4/0 AWG (75 °C) copper conductors.