Size multi-day winter cabin energy reserves with cold-capacity derating
This worked cabin load schedule combines an AC fridge (960 Wh), 240 V/120 V well pump cycles (400 Wh), cabin LEDs + router (650 Wh), and intermittent power tools/microwave (300 Wh) totaling 2,310 Wh/day AC.
At 3 days autonomy, 90% inverter efficiency, 85% DoD, and 90% cool-weather retention, nominal bank demand reaches 10.07 kWh (196.6 Ah at 51.2 V)—solved cleanly by a single 200 Ah or 280 Ah 48 V bank.
Formulas
Usable AC energy (3 days) = 2,310 Wh × 3 = 6,930 WhRequired nominal bank = 6,930 ÷ (0.90 × 0.85 × 0.90) = 10,065.4 WhBank capacity @ 51.2 V = 196.6 Ah (200 Ah group → 1×; 280 Ah → 1×)
Worked example
Over 3 days at 2,310 Wh/day with 90% efficiency, 85% DoD and 90% cool capacity, nominal storage reaches 10,065 Wh (196.6 Ah at 51.2 V); warming to 25 °C reduces demand to 9,059 Wh (176.9 Ah).