Apply NEC 310.16 terminal limits and conduit derating to 48 V DC feeders
Even when THHN/THWN-2 conductors carry a 90 °C insulation rating, NEC 110.14(C) caps termination ampacity at 75 °C for most inverter and breaker lugs above 100 A—requiring a 125 A minimum conductor for a 100 A continuous DC load.
Bundling four or more current-carrying conductors in metallic conduit or elevated garage ambients requires an 80% derating factor, pushing the required raceway conductor upward from 1 AWG to 2/0 AWG copper while keeping a 125 A Class T fuse inside the cable limit.
Formulas
NEC continuous fuse/ampacity target = 1.25 × 100 A = 125 A75 °C raceway copper: 1 AWG = 130 A; at 80% derating, 2/0 AWG = 175 × 0.80 = 140 ARound-trip 25 ft loop = 15.24 m · 2% drop budget @ 51.2 V = 1.024 V
Worked example
A 100 A 51.2 V feeder over 25 ft one-way in raceway at 75 °C lugs screens 1 AWG copper (130 A ampacity, 1.40% drop) with a 125 A Class T fuse; adding an 80% conduit derating factor steps up to 2/0 AWG copper.