Size 48 V battery leads cleanly for 5 kW off-grid AIO inverters
A 5,000 W 230 V off-grid inverter running near 90% conversion efficiency pulls ~108–120 A continuous DC when batteries sit below 49–51.2 V under sustained appliance load.
At 120 A over 2 m one-way, 1 AWG marine copper returns 0.237 V (0.46% loop drop) with a 150 A 125 V Class T fuse, stepping up to 1/0 AWG and 175 A Class T at a 140 A worst-case continuous design point.
Formulas
120 A × 1.25 OCPD = 150 A Class T screen1 AWG 2 m loop (4 m Cu) @ 120 A = 0.237 V (0.46% drop)140 A surge preset = 1/0 AWG (0.220 V, 0.43% drop, 175 A Class T)
Worked example
Over a 2 m one-way run at 120 A (51.2 V), 1 AWG copper keeps voltage drop at 0.46% (0.237 V) with a 150 A Class T fuse; at 140 A, it upgrades cleanly to 1/0 AWG and 175 A Class T protection.