16S CATL 302Ah 48V LiFePO4 Solar Battery Pack Calculator

Calculate 16S1P vs. 16S2P CATL 302 Ah 48 V storage bank specs: 51.2 V nominal, 15.46 kWh, 0.5 C continuous BMS current (151 A) and 88 kg stack mass.

Jump to results

Inputs

Pack layout
Unit specifications

Results

Estimates
Nominal pack voltage51.2 V
Full charge
58.4 V
Discharge cutoff
40 V
Nominal capacity
302 Ah
Nominal energy
15.462 kWh
Unit weight only
88 kg
Equivalent unit resistance
4 mΩ
Unit-limited continuous output
151 A / 7.73 kW
BMS sizing for full unit output
16S · ≥151 A
Pack electrical schematic · 16S1PScroll ↔ · 16S
PACK VOLTAGE 51.2 V 40–58.4 V PACK CAPACITY 302 Ah 15.46 kWh IMPEDANCE 4 mΩ 16× cells CONT. OUTPUT 151 A 7.73 kW max CELL MATRIX ENCLOSURE · 16S1PS1 − +S2 − +S3 − +S4 − +S5 − +S6 − +S7 − +S8 − +S9 − +S10 − +S11 − +S12 − +S13 − +S14 − +S15 − +S16 − + B− B+ BMS · 16S BALANCING & FET ≥ 151 A continuous 17 sense taps (B0–B16) MAIN BUS & PROTECTION REF. 125% fuse ≥ 189 A Interrupt rating ≥ 59 V DC

Cell-limited estimates assume matched units and even current sharing. Set charge, BMS, busbar and thermal limits from your actual hardware.

Engineering Bill of Materials (BOM)
CategorySpecificationQtySizing basis
Cells / Modules3.2 V 302 Ah matched cells (16S1P)16 pcs51.2 V nominal · 15.46 kWh · 88 kg
BMS16S BMS, ≥151 A continuous (charge & discharge)1 unitFull charge 58.4 V · 151 A (0.5C)
Main DC Fuse & HolderClass T 200 A fuse & holder (≥59 V DC)1 set125% of 151 A continuous output @ 58.4 V max
Main DC Cable Run3/0 AWG (85 mm²) copper feeder cable + ring lugs2 runs (+ / −)Sized for ≥189 A pack-to-busbar feeder
Busbars & Interconnects250 A tinned copper cell busbars + terminal covers15 links16S1P interconnects rated ≥189 A
DC Isolator Switch200 A DC battery disconnect switch (≥59 V DC)1 unitService isolation for 51.2 V pack

Size 15.46 kWh energy-dense CATL 302 Ah cells within 0.5 C continuous limits

CATL 302 Ah solar storage prismatic cells provide 15.462 kWh per 16S1P module (88.0 kg bare cells), ~7.8% more storage per pack than 280 Ah cells in almost identical enclosure widths.

Rated at 0.5 C continuous, one 16S1P CATL 302 Ah stack supports 151 A continuous (~7.73 kW DC)—meaning a 10–15 kW hybrid inverter runs coolest with two 16S banks (16S2P / 302 A = 30.92 kWh).

Formulas

  • Pack nominal energy = 51.2 V × 302 Ah ÷ 1,000 = 15.4624 kWh
  • Continuous @ 0.5 C = 302 × 0.5 = 151 A (7,731 W DC)
  • 16S2P energy = 30.9248 kWh · 302 A continuous

Worked example

Sixteen CATL 302 Ah cells in 16S1P store 15.462 kWh at 51.2 V nominal (88.0 kg, 151 A BMS minimum); doubling to 16S2P raises bank storage to 30.925 kWh and 302 A continuous capability.

Frequently asked questions

Is a 200 A BMS safe on a single 16S CATL 302 Ah bank for brief inverter surges?

Yes for brief 10–30 second motor starts, provided sustained inverter draw stays within ~150 A (0.5 C) to limit cell heating and extend cycle life.

How should I match CATL 302 Ah cells before assembling a 16S bank?

Verify internal AC impedance at 1 kHz (0.2–0.3 mΩ) and shipping open-circuit voltage within 5–10 mV, then top-balance all 16 cells in parallel to 3.60–3.65 V.

What enclosure torque checks matter on aluminum busbar studs?

Use calibrated torque settings recommended for M6 studs (~4–6 N·m depending on stud insert) with serrated or Belleville washers—never over-torque soft aluminum threads.