12V 2000W Inverter Cable Gauge & Fuse Size Calculator

Size copper battery cables, voltage drop and Class T or MRBF fuse candidates for a 2,000 W inverter on a 12.8 V LiFePO4 bank.

Jump to results

Inputs

Circuit and voltage drop
Use full charge voltage when screening DC fuses.
Cable and installation
Enter the combined ambient and bundling adjustment.

Results

Estimates
Minimum reference gauge4/0 AWG
Round-trip length
3 m
Fuse target at 125% load
225 A
Copper or aluminum area
107.22 mm²
Calculated drop
0.1 V · 0.79%
Cable loss
18.09 W
Adjusted ampacity
230 A
DC circuit loop schematic · Copper · Raceway4/0 AWG · 0.79% drop
DC POWER LOOP · COPPER · RACEWAY · 75 °C PASS · 4/0 AWG (107.2 mm²) BATTERY / SOURCE 12.8 V Max 14.6 V DC Draw 180 A MAIN FUSE Class T 225 A Ceiling 125 V DC 4/0 AWG · 107.2 mm² Cu 1.5 m 1-way · 0.19 Ω/km @ 60 °C LOAD / INVERTER 12.7 V At load terminals 2,304 W · 180 A Return conductor (4/0 AWG · 3 m round-trip) · Drop −0.1 V VOLTAGE DROP VS. 2% 0.79% Drop 0.1 V / 0.26 V max Loss 18.1 W AMPACITY (100% DERATE) 180 / 230 A 125% fuse target 225 A Fuse cap 230 A
Neighboring gauges
AWGmm²Ω/kmAmpacityDropScreen
2/067.430.296175 A1.25%Outside limits
3/085.030.235200 A0.99%Outside limits
4/0107.220.186230 A0.79%Pass
Main fuse candidates
TypeCurrent candidateExample DC ceiling
Class T225 A125 V
ANL225 A32 V
MRBF225 A58 V

Fuse candidates account for the entered 14.6 V circuit maximum. Check available fault current, interrupt rating, terminals and applicable installation rules.

Engineering Bill of Materials (BOM)
CategorySpecificationQtySizing basis
DC Cable Run4/0 AWG (107.22 mm²) copper cable, 90 °C (raceway)3 m loop (1.5 m × 2)0.79% drop (0.1 V) · 230 A ampacity
Main DC Fuse & HolderClass T 225 A fuse (125 V DC) + compatible holder1 set125% load (225 A) screened @ 14.6 V max
Lugs & Terminations4/0 AWG tinned copper compression lugs + heat shrink4 lugsRated ≥75 °C terminal limit for copper
DC Busbar250 A DC distribution busbar pair with insulated cover1 pair (+ / −)Covers ≥225 A continuous feeder rating
DC Isolator Switch250 A DC load-break isolator (≥15 V DC)1 unitManual disconnect for 180 A 12.8 V circuit

Handle 180 A continuous current safely on a 12 V 2,000 W inverter

High-power inverters on 12.8 V banks pull heavy current: delivering 2,000 W AC at 87% inverter efficiency demands roughly 180 A DC continuously and over 350 A on short motor startup surges. Keeping the inverter within 1.5 m one-way of the battery busbar prevents nuisance low-voltage alarms.

At 14.6 V maximum charging voltage, Class T, ANL and MRBF fuse families are within DC voltage range, though a Class T fuse placed directly near the battery positive terminal provides superior fault-interrupt capability for parallel lithium banks.

Formulas

  • DC current (A) ≈ AC output (W) ÷ (battery V × efficiency)
  • 125% protective screen = 1.25 × 180 A = 225 A
  • Allowable 2% drop at 12.8 V = 0.256 V round trip

Worked example

At 180 A over a 3 m copper loop with 75 °C terminals, the 1.25× screen target is 225 A, returning 4/0 AWG copper with roughly 0.10 V (0.79%) drop and a 225 A fuse candidate.

Engineering references

Frequently asked questions

Why does a 12 V 2,000 W inverter often need 2/0 or 4/0 AWG cable?

High DC current (180 A+) drives thermal ampacity limits and strict sub-0.25 V voltage drop targets even on short runs under 5 feet.

Is a 225 A or 250 A Class T fuse better for a 2,000 W 12 V inverter?

Check the inverter manual and ensure the selected fuse current protects the chosen conductor ampacity (e.g., 230 A at 75 °C for 4/0 AWG) while clearing inverter surge ratings.

Can two smaller parallel cables replace one 4/0 AWG lead?

Follow equipment manufacturer rules and local marine or RV code; paralleled conductors generally require identical lengths, crimps and proper fault protection on each run.